title: "GWU-5 4G LTE Modbus gateway with Ethernet and MQTT | GridBit"
description: "GWU-5 is a DIN-rail communication gateway. It reads the devices on an RS485 Modbus RTU bus and Modbus TCP devices on the LAN port, and connects them to the."
url: "https://www.gridbit.tech/hardware/gwu-5"
language: "en"
translation: "https://www.gridbit.tech/bg/hardware/gwu-5"
---

# GWU-5

4G LTE gateway for Modbus devices, with Ethernet and MQTT

[Request a quote](https://www.gridbit.tech/contact?product=GWU-5)

- **Mobile network, 2G fallback**: 4G LTE Cat 1
- **Modbus RTU and Modbus TCP**: RS485 + Ethernet
- **Supply voltage**: 9 to 24 VDC
- **Operating temperature**: -20 to 60 °C

Overview

## Where it works

GWU-5 is a DIN-rail communication gateway. It reads the devices on an RS485 Modbus RTU bus and Modbus TCP devices on the LAN port, and connects them to the GridBit platform over 4G LTE Cat 1, 2G or Ethernet. It has one digital input and runs on 9 to 24 VDC.

Mounting: 35 mm DIN rail (IEC 60715)

1. Connecting Modbus meters, controllers and sensors to a central system over the mobile network
2. Street lighting cabinets, transformer stations, pump stations and other remote sites
3. Building your own IoT system on a gateway that GridBit manages remotely

GWU-5 gateway, three-quarter view

Datasheet

## Technical data

### Power supply

- **Supply voltage**: 9 to 24 VDC
- **Consumption**: max. 150 mA

### Digital inputs

- **Number**: 1
- **Type**: IEC 61131-2 Type 1

### Modbus RTU

- **Interface**: RS485
- **Protocol**: Modbus RTU
- **Baud rate**: 9600, 19200, 38400, 57600 default 9600
- **Parity**: 8N1, 8E1, 8O1, 8N2 default 8N1

### Modbus TCP

- **Interface**: Ethernet (LAN)
- **TCP port**: 502 default

### Mobile network

- **Standard**: 4G LTE Cat 1 (FDD/TDD), 2G (GSM/GPRS/EDGE)

### Environment

- **Operating temperature**: -20 to 60 °C
- **Storage temperature**: -20 to 80 °C
- **Relative humidity**: below 95 %, non-condensing

### Status LEDs

- POW On Input voltage present
- COM Blinking Connecting to the mobile operator
- COM On Connected to the platform
- DI1 On Digital input 1 closed
- MB On A device on the Modbus bus is missing or faulty

Installation

## Dimensions and connection

Dimensions in mm

Connection diagram

On a 35 mm DIN rail

Systems

## Used in

Street lighting

### [Street lighting management](https://www.gridbit.tech/solutions/street-lighting)

Control and monitor street lighting cabinets from one system, with schedules that follow sunrise and sunset, measurements per phase and alarms for every cabinet.

Learn more

EIM

### [Electrical infrastructure monitoring](https://www.gridbit.tech/solutions/eim)

Sensors, analysers and a gateway turn a secondary substation into a monitored asset. The platform shows the transformer and the low-voltage board in real time, with alarms and reports for the grid operator.

Learn more

[Previous WDT-4 Modbus watchdog relay, fallback to photo sensor or clock](https://www.gridbit.tech/hardware/wdt-4)
[Next GWU-4 2G/4G gateway for Modbus RTU devices, two digital inputs](https://www.gridbit.tech/hardware/gwu-4)

### Transport, warranty and maintenance

- **Transport and storage**: Protect the module from shocks and avoid extreme conditions. Store it in the original packaging.
- **Warranty**: Two years from the date of manufacture against manufacturing defects. Modifications to the product after the publication date of its documentation release the manufacturer from liability. The manufacturer is not responsible for typographical or other errors in the documentation.
- **Maintenance**: Under normal conditions the module needs no maintenance. Light dirt comes off with a dry or slightly damp cloth; for heavier dirt use non-aggressive cleaning products. Always disconnect the power supply first, keep liquids out of the housing and reconnect the power only when the module is completely dry.

## Ask for a GWU-5 quote

Tell us the quantity and the project. We answer with a price and lead time.

[Request a quote](https://www.gridbit.tech/contact?product=GWU-5) [office@add-bg.com](mailto:office@add-bg.com)